日本一级2020免观视频

深圳市众安科电子有限公司

产品详情
HS103 Conventional Sound Strobe 2线非编声光报警器DC24V
市场价 : 0.0
产品详情
产品评论(0)

HS103 Conventional Sound Strobe
SPECIFICATIONS
Working voltage: 9VDC-30VDC.
Alarm Current: ≤ 50mA.
Ambient temperature: -10℃~+55℃.
Ambient humidity: ≤95%RH.
Sound level of alarm : ≥100dB.
Flash Intensity: ≥75CD
Flash Period: <1S
Life of flash light: >40000times
Dimensions: 133mm×115mm×50mm
L ×W×D(With base)
Weight: 141g

BEFORE INSTALLING
This information is included as a quick reference
installation guide. Refer to the control panel installation
manual for detailed system information. If the sound
strobe will be installed in an existing operational system,
inform the operator and local authority that the system
will be temporarily out of service. Disconnect power to
the control panel before installing the modules.
NOTICE: This manual should be left with the
owner/user of this equipment.
GENERAL DESCRIPTION
The Sounder strobe is a kind of audible and visual alarm
device installed in field, which can be activated by fire
alarm control panel in fire control center or by manual
call point installed in field. After activated, it will
generate strong audible/audible and visual alarm signal to
warn people in field.
Design and Wiring
The system designer must make sure that the total current
drawn by the devices on the loop does not exceed the
current capability of the panel supply, and that the last
device on the circuit is operated within its rated voltage.
When calculating the voltage available to the last device,
it is necessary to consider the voltage drop due to the
resistance of the wire. The thicker the wire, the smaller
the voltage drops. Wire resistance tables can be obtained
from electrical handbooks.
INSTALLATION
NOTE: All wiring must conform to applicable local
codes, ordinances, and regulations.
Mounting Indoor Wall or Ceiling Products
1. Drill 2 screw holes apart from each other 60mm
-80mm on the wall.
2. Connect field wiring to terminals
3. To attach product by two mounting screws.
4. Secure product by tightening the two mounting screws
in the front of the product housing.